Why this calc exists
Formwork design hinges on the lateral pressure that fresh concrete exerts on the shutters. Two extremes bound the problem: zero pressure (if concrete behaved like a solid) and full hydrostatic head (γ·h, if concrete behaved like water). Reality is between, governed by placement rate, temperature, and chemistry.
ACI 347R-14 Eq 2.2 captures this with an empirical formula that gives p_max = Cw·Cc·[7.2 + 785·R/(T+17.8)] kPa, where R = placement rate (m/h), T = concrete T (°C). The 30 kPa floor and full hydrostatic cap (γ·h) bracket the result. The formwork pressure calculator applies the SI form with the validity bounds.
Code references (with provenance)
- ACI 347R-14 — Guide to Formwork for Concrete (Eq 2.2 SI form). The primary reference.
- CIRIA C544 — Concrete pressure on formwork (UK alternative; gives similar but slightly different values).
- IS 14687:1999 — Falsework and formwork for concrete structures — code of practice (Indian context).
Worked: column, 3 m tall, R = 2 m/h, T = 30 °C
Eq 2.2: p_max = 1.0·1.0·[7.2 + 785·2/(30+17.8)] = 7.2 + 1570/47.8 = 7.2 + 32.8 = 40.0 kPa.
Hydrostatic cap: γ·h = 24 × 3 = 72 kPa.
30 kPa floor: 30 < 40, so the Eq value stands.
Design pressure: 40 kPa (lower of Eq and hydrostatic, since 40 < 72).
Field notes (what trips people up)
- Outside validity bounds, use hydrostatic. ACI 347R's Eq is calibrated for slump ≤ 175 mm, internal vibration, R ≤ 2.1 m/h (columns), height ≤ 4.2 m. SCC mixes with slump 600+ mm behave differently; tall walls (> 4 m) often reach hydrostatic; very high placement rates push toward the hydrostatic cap.
- 30 kPa floor is conservative. For low walls (≤ 1 m), the equation can predict < 30 kPa; the code imposes 30 kPa minimum to account for construction vibration, workers on top, and impact loads.
- CIRIA vs ACI. CIRIA C544 gives slightly higher pressures for SCC and lower for low-heat mixes. ACI is more conservative for normal mixes; CIRIA for SCC. Site practice: pick the more conservative of the two.
- Formwork ties and walers must resist this pressure over the full panel area. Under-design of ties is the #1 formwork failure mode.
Worked example
Site: 4 m lift of shear wall, R = 1.5 m/h, T = 28 °C, OPC no retarder, internal vibration.
Eq: 7.2 + 785·1.5/(28+17.8) = 7.2 + 25.7 = 32.9 kPa.
Hydrostatic: 24 × 4 = 96 kPa.
Design: 32.9 kPa (Eq value), with 30 kPa floor → 32.9.
Field-checklist blocks
A short questionnaire, an inspector's checklist, and three worked examples that show how the placement rate on the pour card decides the size of the tie.
Questionnaire — ask before the shutters are closed
- What is the planned placement rate R in m/h, and is it within the 2.1 m/h the ACI equation is calibrated for on columns?
- What is the concrete temperature at placement, since R and T both feed the equation?
- Is the mix inside the validity bounds — slump at or below 175 mm with internal vibration, rather than an SCC mix at 600 mm slump?
- Is the lift height within 4.2 m, and if it is taller, does the wall reach hydrostatic?
- What is the height of the element, so the hydrostatic cap γ·h can be computed and set against the equation value?
- Has the more conservative of ACI 347R and CIRIA C544 been taken, given that the two diverge for SCC and low-heat mixes?
- Have the ties and walers been designed for the full panel area at this pressure? Under-design of ties is the number one formwork failure mode.
Inspector's checklist — what to verify before and during the pour
- R and T recorded for the pour, taken from the batching and placement plan rather than assumed.
- Equation value computed and set against the hydrostatic cap γ·h and the 30 kPa floor.
- Validity bounds checked on the face of the calculation — slump, vibration method, placement rate, height.
- Design pressure written on the shutter drawing and matched to the tie spacing and waler section actually used on site.
- Tie spacing, size and capacity verified against that pressure over the full panel area.
- Placement rate watched through the pour, and the pour slowed if it outruns the design rate.
- SCC and tall-wall cases taken to CIRIA or to hydrostatic rather than through the ACI equation.
What happens if… three worked examples
What happens. Eq 2.2 gives p_max = 7.2 + 785 × 2/(30+17.8) = 40.0 kPa. The hydrostatic cap is 24 × 3 = 72 kPa, and the 30 kPa floor does not bite because 40 is above it.
Likely outcome. Design pressure 40 kPa, the lower of the equation value and the hydrostatic head. The shutter, the ties and the walers get sized to that figure.
Correction. None, provided the placement rate at site stays near 2 m/h and the mix is within the calibrated slump and vibration assumptions.
What happens. Eq 2.2 gives 7.2 + 785 × 1.5/(28+17.8) = 32.9 kPa, against a hydrostatic 24 × 4 = 96 kPa. The 30 kPa floor sits just below, so 32.9 kPa stands.
Likely outcome. The design pressure is 32.9 kPa, only a little above the floor. The margin is thin, and the whole result rests on the placement rate actually being 1.5 m/h on site.
Correction. Monitor the rate through the pour and slow it if it climbs. A rate above the assumed figure pushes the pressure up quickly, and it is the ties that fail first.
What happens. The ACI equation is applied to a mix with 600 mm slump, well outside the 175 mm it is calibrated for, or to a wall above 4.2 m.
Likely outcome. The equation underestimates, because SCC behaves much closer to a liquid. The shutter is designed for a number the concrete will not respect, and the failure shows as a bulge in the panel with grout leaking through the joints.
Correction. For SCC use CIRIA C544 or a hydrostatic assumption, and for tall walls assume γ·h. Outside the validity bounds, hydrostatic is the safe answer.
FAQ
Why does placement rate matter?
Faster placement means more fresh concrete on top of partially-set concrete — the lower layers behave more like liquid. Slow placement lets the bottom set and not contribute to lateral pressure.
What about superplasticizer / SCC?
SCC behaves much closer to liquid; the ACI equation underestimates. For SCC, use CIRIA C544 or a hydrostatic assumption (γ·h).
Why is the formula metric-unfriendly in some sources?
ACI 347R has separate IP and SI versions. The IP version uses p in psf, R in ft/h, T in °F. We use the SI form: p in kPa, R in m/h, T in °C. The constants 7.2 and 785 are the SI conversion.
Related reading & tools
- ../calculators/formwork-pressure.html — Formwork Pressure calculator
- formwork-engineering-is14687.html — Formwork Engineering — IS 14687 (blog)
- formwork-types-and-liners.html — Formwork Types and Liners (blog)
Technical updates, not sales emails
One email when a new article goes out on concrete technology, QA/QC and construction quality. No promotions, and your address is never sold or passed to advertising networks. Subscribing is separate from making an enquiry.